Product Description

Generator Controller

Introduction: The microcontroller based Generator Controller is designed to fulfill the all requirements of customer. Please read the instructions below for detail of controller.

Display Features: Voltage – Frequency – Current – RPM - Engine Run Time – Service due time - Oil pressure – Temperature - Fuel Level – Battery Voltage - Fault history.

Mains Voltage : R voltage – Y Voltage - B Voltage.

Mode: The controller can be operated 3 modes. Fully Auto – Only Stop - Manual.

Warnings: Low Battery warning – High Battery Warning – Alt. charge fail.

Safety Features:

Alternator Safety Features: Over under voltage trip - Over under Frequency trip – Over under RPM trip – Over current trip – Short Circuit Trip.

Engine Safety Features : LLOP trip – High Temperature trip – Radiator water low trip – Low fuel trip - Alt. charging fail/ V-Belt trip – Emergency Stop.

Sensor Error Tripping : LLOP sensor error trip –HWT sensor error trip – LFL sensor error trip.

(All the features mentioned above can be set manually. For more details please read the instructions given below. Functions may vary depending upon the model.)

Working of switches :

  • Settings can be changed only when the generator is in idle mode. Please use the under mentioned procedure to change the settings.
  • Menu button is used to enter the menu. The menu is protected with passcode and to enter the menu 1234 passcode is required to be entered.
  • Start button is used to increase the value. Stop button is used to decrease the value. Ok button is used to save the settings.
  • After saving the settings menu button works as return button to come back to the home screen. during home screen mode ok button works as Scroll button to rotate and pause the screen.
  • Reset Button is used to reset the unit during warning and fault.
  • Start button is used to start the generator during home screen mode.
  • Stop button is used to stop the generator in manual mode during running condition. If Auto stop is enabled the generator will stop automatically either it has been started manually and if Fully Auto is enabled the generator will start and stop automatically. The unit can also be operated with wired remote for changing the mode of controller and to start and stop the controller in manual mode.

Settings

Main menu

Sub menu

Sub menu1

Value

Set vlaue

display Settings

Page scrool Time


1 to 20 sec

10 sec


Fault history


20


Battery Settings

Low voltage check



Enable


If Enable

Low voltage vaue

9 to 50 volts

12 volts


High voltage Check





If enable

High voltage value

9 to 50 volts

14.5 volts



High voltage delay

1 to 30min

2 min.


Alt .chag /v-belt check

If enable





Alt chg./v-belt value

9 to 50 volts

12 Volts



Alt cha-/v-belt dalay

10 to 120 sec

10 sec

Alternator settings






General Settings






Alternator fitted

Yes/no

yes



If yes





No. of Poles

2./4/6/8

4


Voltage monitoring

Low voltage check

If enable




Low voltage value

150 to 200 volts

180 volts



Low voltage delay

5 to 60 sec

5 sec



Low voltage bizz

Enable/disable

disable


High voltage check


If enable




High voltage value

200 to 300 volts

260 volts



High voltage delay

0 to 60 sec

15 sec



High voltage buzz

Enable / disable

disable


Frequency monitoring

Low frequency check




If enable

Low frequency value

40 to 50 Hz

45 Hz.



Low frequency delay

5 to 60 sec

15 sec.



Low frequency

Enable / disable

disable


High frequency check


If enable









High frequency vlaue

50 to 60 HZ .

55 HZ



High frequency delay

5 to 60 sec

15 sec


Current monitoring

Select CT Ratio


1/1


Over current check





If Enable

Over current value

10 to 300 amps.

55 amps.



Over current action

E -trip/shutdown

Shutdown



Over current delay

50 to 60 sec

15 sec



Over current buzz

Enable /disable

disable


Short circuit check


Enable /disable

Enable

Timer settings

Crank

Crank timing

5 to 9 sec

1.0 sec



Oil pressure O.C check

Enable / disable

Enable



disengage voltage

0 to 75 volts

15 volts


Applicable in Auto Mode

Manins of wait time

0 to 120 sec

5 sec



Total cranks

10

5



Interval between cranks

3 to 30 sec.

10sec


Main menu

Sub menu

Sub menu 1

Value

Set value

Timer settings

Auto stop





If enable

Mains on wait time

5 to 180sec.

30 sec.



Auto stop time

5 to 60 sec.

15 sec.



Fail to stop delay

5 to 120 sec.

25 sec


Hooter

Hooter on time

3 to 60 sec

10 sec.

Engine settings

Low oil pressure





If enable

Low oil pressure delay

0 to 90 sec.

15 sec.



Type of sensor

digital /Analog

Both



Low oil pressure check

Enable /disable

Enable



Low oil check

Enable/ disable

Enable



Low oil pressure value

0 to Sbar

3.0 bar




Low oil pressure buzz

Enable / disable

disable



High temperature





If enable

High temp delay

0 to 90 sec.

15 sec.



Type of sensor

digital / Analog

Both



High temp analog check

Enable / diable

Enable



High temp value

25 to 105 degree

92 degree



High temp.buzz.

Enable /disable

disable


Low fuel level





If Enable

Low fuel level delay

0 to 90 sec

15 sec.



Type of sensor

Analog / digital

Both



Low fuel analog check

Enable /disable

Enable



Low fuel level value

10 to 60%

20%



Low fuel level buzz

Enable /disable

disable



Low fuel level warning

Enable /disable

Enable



Fuel theft alarm

Enable / disable

Enable


Low radiator water





If Enable

Low water delay

15 to 120 sec.

15 sec.


Emergency stop





Engine service due





If Enable

Service due value


300 hours



Serivce due warining

Enable /disable

Enable



Service due buzzer

Enable/disable

disable




Enable / disable

Enable

Mains settings

Low voltage check





If enable

Low voltage set

100 to 200 volts

150 volts



Low voltage resume

300 to 200 volts

155 volts



Low voltage delay

0 to 30 sec.

5 sec.


High voltage check

High voltage value

200 to 300 volts

255 volts



High voltage resume

200 to 300 volts

250 volts



High voltage delay

2 to 30 sec

4 sec



double phase check

Enable/ disable

Enable

Contactor settings

Manis contactor





If enable

Contactor on delay

5 to 120 sec.

5 sec.


Generator contactor





If enable

Contactor on volts

180 to 280 volts

200 volts



Contactor on delay

2 to 120 sec

2 sec



Contactor off delay


3 sec